Code Hunter – Protection, 2017 NEC

0
287
Code Hunter

To play this game, you need a sharp eye, a quick mind and a 2017 National Electrical Code book.
(Fill-in-the-blank questions are looking for the exact word(s) used in the NEC.)

Questions

1) Where a panelboard is supplied through a transformer, the overcurrent protection required by 408.36 shall be located on the __________ side of the transformer.

A) supply
B) primary
C) midpoint
D) secondary

2) Where overcurrent protection is provided as part of the industrial control panel, the supply conductors shall be considered as either feeders or __________ as covered by 240.21.

A) taps
B) splices
C) branch circuits
D) transformer secondary conductors

3) Where corrosion protection is necessary, and the conduit is threaded in the field, the threads shall be coated with an approved electrically conductive, corrosion-resistant compound.

A) Listed
B) Marked
C) Approved
D) Identified

4) Where a feeder overcurrent device is not __________, branch-circuit overcurrent devices shall be installed on the load side, shall be mounted in a readily accessible location, and shall be of a lower ampere rating than the feeder overcurrent device.

A) provided
B) installed
C) accessible
D) readily accessible

5) Flexible cord used in extension cords made with separately listed and installed components shall be permitted to be supplied by a branch circuit in accordance with the following: 20-ampere circuits — __________ and larger

A) 8 AWG
B) 12 AWG
C) 16 AWG
D) 24 AWG

6) Instruments, pilot lights, voltage (potential) transformers, and other switchboard or switchgear devices with potential coils shall be supplied by a circuit that is protected by standard overcurrent devices rated __________ or less.

A) 15 amperes
B) 20 amperes
C) 100 amperes
D) 800 amperes

7) Equipment for __________ circuits (including transfer switches, transformers, and panelboards) shall be located either in spaces fully protected by approved automatic fire suppression systems (including sprinklers, carbon dioxide systems) or in spaces with a 2-hour fire resistance rating.

A) feeder
B) fire pump
C) emergency
D) branch-circuit

8) When does the NEC allow a 3 AWG copper wire to be protected by a 600-ampere breaker? When it is a:

A) Motor circuit conductor
B) Transformer primary conductor
C) Nickel-coated copper conductor
D) Hospital branch circuit conductor

9) The measured supply voltage at the service equipment in my facility is 610 volts, but the nominal system voltage is 600 volts. Does the NEC allow me to use conductors rated 600 volts?

A) Yes
B) No

10) Does the NEC prohibit me from installing my service equipment in the center of my warehouse?

A) Yes
B) No

Answers

1) D, Secondary. The requirement in 408.36(B) states that the panelboard protection be located on the secondary side of the transformer unless primary protection is provided in accordance with the limitations in 240.21(C)(1). The exception allows primary protection only for 2-wire, single-phase and 3-wire, delta-delta connected transformers in certain cases.

2) A, taps. A single main overcurrent protective device located within the industrial control panel is permitted by 409.21(B)(2) to satisfy the requirement for overcurrent protection in 409.21(A). For sizing the conductors feeding that overcurrent protective device, the provisions in 240.21 must be used.

3) C, Approved. Corrosion protection is required by 300.6(A) both inside and outside of ferrous metal equipment, and the use of an appropriate compound is specifically required on field-cut threads. In the 2014 NEC, an Informational Note was added indicating that “field-cut threads” are those made anywhere other than at the factory where the product was listed.

4) D, Readily accessible. Section 225.40 requires that readily accessible branch-circuit overcurrent devices be installed on the load side where the feeder overcurrent device has restricted access. This language works with the language found in 225.35 and 230.92, which allow restricted access to the supply disconnecting means in multiple-occupancy buildings under continuous building management supervision.

5) C, 16 AWG. Note that the language in 240.5(B)(4) requires each component of the field assembled extension cord to be listed.

6) A, 15 amperes. Section 408.52 requires that the overcurrent devices protecting these types of devices be limited to 15 amperes, unless interruption of the circuit could create a hazard. In that case, higher rated overcurrent devices are allowed, and short-circuit protection is required. Special types of enclosed fuses are also permitted for ratings of 2 amperes or less.

7) A, Feeder. Section 700.12(D)(2) requires that in assembly occupancies for not less than 1000 persons or in buildings above 75 ft. in height, emergency system feeder equipment must be protected by an automatic fire suppression system or by being located in a space with a 2-hour fire resistance rating.

8) A, Motor circuit conductor. 430.52(C) and Table 430.52 allow the maximum rating or setting of motor branch-circuit short-circuit and ground-fault protective devices to be much higher than in most normal circuits. This is to allow for the high inrush current (also known as locked rotor current or starting current) experienced when starting a motor. Assume we have a 60 hp, 460-volt, 3 phase motor with a full-load current (FLC) of 77 amperes; 430.22 would require a conductor with an ampacity of 125% the FLC, or 96.25 amperes. A 3 AWG copper conductor has an ampacity of 100 amps in the 75C column of Table 310.15(B)(16). In Table 430.52, an instantaneous trip breaker can be up to 800% of the FLC of the motor; 800% of 77 amperes would be 616 amperes. Although 430.52(C)(1) Exception No. 1 allows us to round up to the next standard ampere rating overcurrent device, which would be 700 amperes, it is likely that a 600-ampere device would be sufficient.

9) A, Yes. Section 110.4 states that the voltage rating of electrical equipment shall not be less than the nominal voltage of a circuit to which it is connected. Actual voltages measured at any point in a system can vary depending on the supply voltage from the utility and the load on the system at any point in time. 300.2(A) states that the wiring methods in Chapter 3 shall be used for 1000 volts, nominal, or less where not specifically limited in some section of Chapter 3.

10) B, No. Section 230.70(A)(1) requires that the service disconnecting means be readily accessible and located either outside the building or inside nearest the point of entrance of the service conductors; however, we can use 230.6 to keep our conductors “considered outside the building” until they enter the equipment room located in the middle of the warehouse. For example, we could use 230.6(4) and install the service conductors in a conduit 18” under the building until they turn up into the equipment room.

Christel Hunter is director of codes and standards for Cerro Wire. Chris is a senior associate member of IAEI and serves as a board member for the Southern Nevada Chapter of IAEI and the Las Vegas Section of IEEE. Chris also serves on NEC CMP-6, and the CE Code Part I committee, Sections 4 and Section 12.

Randy Hunter is an instructor and consultant specializing in electrical code and installations, and co-owner of Hunter Technical Services. He holds twelve inspections certifications from IAEI, ICC and IAPMO. He is the IAEI Southwestern Section secretary and Southern Nevada IAEI Chapter president. Randy has been a master electrician since 1988.

Bonus Question
Are there any cable wiring methods that can be directly buried under a building without being protected by a raceway?

A) Yes
B) No

Answer: A, Yes. Section 300.5(C) Exceptions 1 and 2 were added in the 2011 NEC cycle to allow Type MC cable and Type MI cable to be installed under buildings without being in a raceway, so long as they are suitable for the application.

Previous articleThe 5 ft. Ground Rod and its little-known use in the NEC
Next articleA simple approach to inspecting a complex PV installation
Christel Hunter is director of codes and standards for Cerro Wire. Chris is a senior associate member of IAEI and serves as a board member for the Southern Nevada Chapter of IAEI and the Las Vegas Section of IEEE. Chris also serves on NEC CMP-6 and CMP-7, the CE Code Part I committee and Sections 4 and 12 subcommittees, and many other industry committees. She is a certified standards professional, master electrician, and LEED accredited professional. Randy Hunter has over thirty years’ experience in the electrical industry including working in the government, contracting and manufacturing sectors. He is an instructor and consultant specializing in electrical code and installations, and co-owner of Hunter Technical Services. He holds twelve inspections certifications from IAEI, ICC and IAPMO. He is the IAEI Southwestern Section secretary, Southern Nevada IAEI Chapter president, former principal member on NEC CMP-6 and CMP-17, voting member of UL 1563 (Electric Spas, Equipment Assemblies, and Associated Equipment), and a former member of the IAPMO Product Certification Committee and Standards Review Committee. Randy has served on several Southern Nevada local code committees and electrical licensing committees and has been a master electrician since 1988. Prior to that, he designed and built computer numerically controlled (CNC) machine tools.

LEAVE A REPLY

Please enter your comment!
Please enter your name here