Hazardous Gases and Vapours, Section 18

Reading Time: 2 minutes

The Canadian Electrical Code, Section 18 covers electrical equipment and wiring in locations where ignition of flammable gases, vapours, dusts and fibres could result in fires or explosions. Such places are identified as hazardous locations. To minimize risks, they are classified as to the levels of risk. Electrical equipment and wiring requirements are more stringent for higher risk locations. This article discusses hazardous locations and equipment identification for flammable or explosive gases and vapours.

Where flammable gases and vapours are present, locations are classified as Class I by Rule 18-004. Under the IEC Zone system of classification, Rule 18-006 further divides Class I locations into three Zones depending on the levels of risk:

Zone 0 – flammable gases or vapours are present continuously or for a long time;

Zone 1 – flammable gases or vapours are likely or next to Zone 0;

Zone 2 – flammable gases or vapours are unlikely and may only be present for a short time or the location is next to a one 1 with positive pressure ventilation in Zone 2.

There is a second method of classifying Class I locations. Under the North American system of classification, Rule 18-006 divides hazardous locations into two Divisions:

Division 1 – an explosive gas atmosphere may exist continuously, intermittently or periodically;

Division 2 – an explosive gas atmosphere is unlikely, may exist for only a short time or the location is next to a Division 1 with positive pressure ventilation in the Division 2.

The North American system of classification is specified in Rule J18-006, found in Appendix J of the Canadian Electrical Code.

As indicated in Rule 18-000, the Zone classification method must be used to classify new, first-time facilities where hazardous gases and vapours will be present. But Rule 18-000 also permits the continued use of the Division system of classification for additions or modifications to existing facilities previously classified by the Division method.

Electrical equipment and wiring is selected for Class I locations by Zone or Division and by atmospheric groups. Under the IEC Zone system, atmospheric groups are designated by Rule 18-050 as Groups IIA, IIB and IIC for a range of gas and vapour groups. For equipment approved under the North American Division system, the same gases or vapours are identified as atmospheric Groups A, B, C or D.

Hazardous gases and vapours may have different characteristics and, therefore, equipment tested and approved for use for one atmospheric group will not provide the required protection when misapplied. If, for example, electrical equipment approved for gasoline is used where acetylene is present, the equipment will not provide the necessary protection against fires and explosions.

For obvious reasons, Class I electrical equipment must also have maximum surface temperatures lower than the minimum ignition temperatures of applicable gases vapours. Rule 18-052(4) contains a list of temperature codes, T1 to T6 for marking electrical equipment to identify maximum surface temperatures. It would be erroneous to install heat producing equipment (for example, lighting) where gases having minimum ignition temperatures below the maximum surface temperatures of the luminaires are present. A fire or explosion would surely result.

Rule 18-052 specifies that electrical equipment must also be clearly marked to show where it can be installed. Class I electrical equipment is marked for Class, Zone or Division, atmospheric group and maximum surface temperature, but minimum marking requirements between the IEC and the North American systems may be somewhat different.

As with previous articles, you should always consult with the electrical inspection authority in each province or territory for a more precise interpretation of any of the above.

Tagged:
About the Author

Leslie Stoch, P. Eng, is principal of L. Stoch & Associates, providing electrical engineering and ISO 9000 quality systems consulting. Prior to that, he spent over 20 years with Ontario Hydro as an electrical inspection manager and engineer. Les holds a B. S. in electrical engineering from Concordia University in Montreal.