Voltage drop is only mentioned in some sections of the NEC as informational notes, and is required to be calculated in other sections of the Code. These sections are 210.19(A) Informational Note 4, 215.2(A)(1) Informational Notes 2 and 3, 310.15(A)(1) Informational Note 1, 647.4(D), 310.60(B) Informational Note 2, 455.6(A) Informational Note, and 695.7. Permitted or required amounts of voltage drop may range from 1.5 to 15 percent of the feeder or branch-circuit voltage. Five percent maximum is generally suggested on a circuit. Informational notes are not mandatory Code requirements, but are explanatory material intended for informational purposes only [see 90.5(C)].
However, manufacturer’s installation instructions, which are required to be followed in 110.3(B), often require a minimum voltage rating to be maintained in order for a particular type of utilization equipment to function properly in the manner intended by the manufacturer, and to be listed by an electrical equipment nationally recognized testing laboratory. To perform voltage drop calculations, it is essential to have the following information: 1) the k-factor, 2) the length of the feeder or branch circuit to the load, 3) the amperage load of the circuit, and, of course, 4) the circuit voltage. The k-factor is a multiplier representing the DC resistance for a given size conductor 1,000 feet long and operating at 75°C. From this information, the code user can find either the minimum size conductor needed to carry the load (measured in circular mils or kcmils), and/or the percentage of voltage drop.
The formulas included here are based on conductor dc resistance values provided in Chapter 9 Table 8 of the NEC, and are viewed as generally acceptable for voltage drop calculations. Table 8 is based on 75C/167F, and provides a k-factor constant of 12.9 for copper, and 21.2 for aluminum conductors. — See note below.
For example, to find the k-factor, you multiply the resistance of the conductor per foot by the circular mil of the conductor. Remember that Table 8 states resistance in ohms per 1,000 feet. For voltage drop calculations when copper wire is used, be sure to select the value from the “uncoated copper” column, as most copper conductors are uncoated. To be “coated” means that there is a tin or other type of coating on the copper conductor, which changes its resistance value. If a conductor is “coated,” then use the “coated” column resistance value. Remember that “coated” does not refer to the conductor installation. Note the following examples.
For Copper Wire, use the dc resistance measured in ohms from Chapter 9, Table 8:
The dc resistance of a 1,000 kcmil copper conductor is 0.0129 ohms per 1,000 feet.
(0.0129 ohms per 1,000 feet divided by 1,000
= .0000129 ohms per foot)0.0000129 ohms per foot x 1,000,000 circular mils = 12.9 k-factor — for copper wire
For Aluminum Wire, the dc resistance measured in ohms per 1,000 feet of conductor from Chapter 9, Table 8:
(0.0212 ohms per 1,000 feet divided by 1,000
= .0000212 ohms per foot)0.0000212 ohms per foot x 1,000,000 circular mils
= 21.2 k-factor — for aluminum wire
Note: It is important to note that to find the k-factor, you multiply the resistance of the conductor per foot by the circular mil sizes of the conductor. For any copper or aluminum conductor found in Chapter 9, Table 8, the k-factor will roughly be 12.9 or very close to it for copper, and 21.2 or very close to it for aluminum. Therefore, these two amounts are chosen as k-factor constant values for uncoated copper or aluminum conductors operating at 75C/167F ambient temperatures and rated amperage.
75C/167F temperature rating is often used in today’s electrical circuits, as most new lugs in electrical distribution equipment and utilization equipment are rated 75C/167F; and 90C/194F rated conductors are used at the 75C ampacity because of the termination requirements found in 110.14(C).
The formula used is also generally acceptable for
60C/140F conductor installations.
Voltage drop is calculated for single-phase installations with the understanding that the current will be returning from the load either from a line-to-line or line-to-neutral load; therefore, the multiplier 2 is added into the formula for the resistance of the conductor to the load and back. This is necessary to complete the circuit, and to clear a fault, keeping 250.122(B) in mind, which will be discussed later.
The formula for three-phase installations uses 1.732 instead of 2 as the multiplier. Current flows out to the load and back on the phase conductors.
Once the volts dropped have been determined, use the formula below to determine the percent of voltage drop for the circuit or system.
Example 1: 7.2 volts dropped ÷ 240 volts (1 phase) = 3% voltage drop
Example 2: 24 volts dropped ÷ 480 volts L-L = 5% voltage drop
Choose a formula based on the conductor size used, or the maximum amount of voltage drop acceptable to the AHJ. (3%, 5%, etc.)
VOLTAGE DROP FORMULAS
Volts dropped
= 2 x Length of conductors to load x k-factor (copper or aluminum) x I (amperage) ÷ The circular mils or kcmils of the conductor used
Voltage Drop Formulas for 3-phase Installations:
Volts dropped =
1.732 x Length of conductors to load x k-factor (copper or aluminum) x I (amperage) ÷ The circular mils or kcmils of the conductor used
To determine size in circular mils required (single-phase) = 2 x L x K x I ÷ % voltage drop
To determine size in circular mils required (three-phase) = 1.732 x L x K x I ÷ % voltage drop
These formulas may be used to determine the maximum length of a conductor, the circular mil size needed for a conductor, or the voltage drop in a system or circuit.
Voltage-Drop Formulas
Where
VD = actual volts dropped (not percentage)
K = assumed specific resistance
L = length of run to load
I = load in amps
CM = area of wire, circular mils
Note: For 3-phase formulas, replace the multiplier 2 with 1.732.
2 x K x I x L ÷ CM = VD
2 x K x I x L ÷ VD = CM
(CM x VD) ÷ (2 x K x I) = maximum length
(CM x VD) ÷ (2 x K x L) = maximum I (amps)
Note: To find k-factor, multiply resistance per foot of conductor by circular mils.
- Go to Chapter 9, Table 8
- Find 1 AWG
- In Circular Mils column for 1 AWG, find 83,690
- Go to Direct Current Resistance at 75°C (167°F), Table 8
- Go to Column ohm/kFT. For 1 AWG, find 0.154 ohm/kFT
- (.154 / 1000) = .000154
Example: K for 1 AWG copper at 75°C = .000154 x 83690 = 12.9
Note: Chapter 9 Table 8 dc resistance values for k-factor and voltage drop on ac circuits are used for simplicity and consistency. Resistance values for a given size wire in Chapter 9 Table 8 are very close to the values given in Chapter 9 Table 9, regardless of which wiring method is used.
Excerpted from IAEI’s Ferm’s Formulas and Calculations Book, 2014.









Find Us on Socials