Photos 1a and 1b. A residential PV plan that could not be approved because the maximum overcurrent protection permitted by NEC 240.4(D)(7) is 30 amps for the 10 AWG conductors. The 7.6kW inverter requires a minimum circuit breaker rating of 40 amps.
Leave a Reply
You must be logged in to post a comment.





Leave a Reply