Here is a quick navigation guide to Section 210.8 of the 2017 National Electrical Code and the 2020 National Electrical Code.
Some installers of electrical equipment have a bit of difficulty in differentiating ground fault circuit interrupters and ground-fault protection. And what is the difference between a typical overcurrent protective device and a ground-fault circuit interrupter?
To play this GFCI quiz, you need a sharp eye, a quick mind, and a 2020 National Electrical Code book. The 2020 NEC can be accessed for free at nfpa.org/70.
Applying proper mitigation ideas for reducing flood loss in electrical systems will not only reduce future damage but also aid recovery after flooding.
During a disruption in electrical service, there are various responsibilities that the utility and homeowner have regarding safe delivery of electricity. This sometimes-contentious issue involves a defined term found in Article 100 of the 2017 National Electric Code (NEC) known as the “service point.” Which begs the question, “How well do you know your electrical service point?”
These voltage drop formulas are based on conductor DC resistance values and are viewed as generally acceptable for voltage drop calculations.
Wiring methods for Class I, Division 2 locations are addressed in Section 501.10(B) of the NEC. Here, in addition to those wiring methods that are permitted for Class I, Division 1 installations in Section 501.10(A), the NEC covers other wiring methods that are permitted for Class I, Division 2.
A stray current is a flow of electric current through unintended conductors such as building structures, electrical grounding or bonding conductors, or other equipment due to electrical supply system imbalances or improper equipment hookup.
The benefit of group motor installations is that only one branch-circuit overcurrent protective device (fuse or listed inverse-time circuit breaker) is required to provide short-circuit protection for all motor controllers or overload protection devices in the group.
Zone-selective interlocking (ZSI) has been in practical use since the mid-1980s. This technology was created to speed up the tripping time for some faults within a zone of protection without sacrificing selective coordination and interjecting nuisance tripping into the system.