Updates: Grounding PV Systems and Fine Stranded Conductors

Grounding

In the “Perspectives on PV” article in the September-October 2004 issue of the IAEI News, the subject of grounding PV systems was covered in some detail. In the March-April 2005, IAEI News, we discussed the changes to Article 690 that appear in the 2005 National Electrical Code. As normally happens over the three-year code development cycle, new thoughts and ideas come to the forefront about how things should be done. Here are some of those thoughts as they apply to grounding smaller PV systems with single inverters sized below about 10 kW. Figure 1 shows the dc grounding for a PV system as spelled out in Section 690.47 of NEC-2005 and as described in the above-mentioned article. Inspector Russ Coombs of Bakersfield, California, suggested that if the ac ground rod cannot be found, then the dc grounding electrode conductor might be spliced (irreversibly) to the ac grounding electrode conductor. I think this is a good suggestion because in many older buildings, the ac grounding electrode is buried in non-accessible locations.

 

PV system designers, PV integrators and installers are always looking for ways to meet the code safety requirements, install the system at the lowest cost, and make the system look good. The grounding system shown in figure 2 has been proposed as an alternate grounding system to meet most of the NEC requirements for grounding these systems. There is no dc grounding electrode (ground rod) located at the inverter. An unspliced 8 AWG (if allowed, based on the type of existing ac grounding electrode) bare or insulated conductor (marked green) is routed from a grounding terminal in the inverter along with the ac inverter output circuit conductors to and through (no stopping) to the ac ground rod. In this example, the 8 AWG conductor serves as both the dc grounding electrode conductor (unspliced, minimum size) and the ac equipment-grounding conductor. It should be noted that all grounding terminals and lugs (equipment-grounding and grounding electrode conductor) are electrically connected together in the inverter and may generally be used interchangeably depending on the size of the conductors they will accept.

Figure 1. Shows the dc grounding for a PV system as spelled out in Section 690.47 of NEC-2005 and as described in the above-mentioned article.

 

Figure 2. This grounding system has been proposed as an alternate grounding system to meet most of the NEC requirements for grounding these systems.

This method only works on the smaller string inverters where the ac equipment grounding conductor is 8 AWG or less and the ac grounding electrode is not something like a UFER (concrete-encased electrode) that may require a 4 AWG grounding electrode conductor. It is usually not appropriate for the 10 kW and larger three-phase inverters.

Multiple, Small String Inverters

Where multiple small inverters are installed in a single location, it is probably best to install a 6 AWG (if allowed based on the type of grounding electrode) bare, grounding electrode conductor from the first inverter in the set to a dc grounding electrode, which is then bonded to the ac grounding electrode. As allowed by NEC-2005, this dc grounding electrode conductor may also be routed and connected directly to the ac grounding electrode. If the ac ground rod cannot be found, then this conductor might be spliced (irreversibly) to the ac grounding electrode conductor. This dc grounding electrode conductor is routed beneath each of the other inverters in the set. A short, 6 AWG grounding electrode conductor is connected to a grounding terminal in each of the other inverters and then irreversibly spliced to the dc grounding electrode conductor running beneath each inverter (see figure 3). In this manner, only one dc grounding electrode conductor is required for the entire set. This is similar to the way multiple service disconnects are grounded in an apartment complex as shown in Exhibit 250.28 in the 2002 NEC Handbook.

Figure 3. Grounding multiple small inverters

Lightning Surge Protection

PV installers should note that the single-inverter grounding method runs the dc negative grounding system and the dc equipment-grounding conductors all the way back to the ac grounding electrode along with the ac output conductors from the inverter. Lightning induced surges may also travel this path and this may increase the possibility of lightning-induced surge damage to the PV equipment with this method of grounding the dc systems. Placing a dc grounding electrode at the inverter (bonded to the ac grounding electrode) may help to reduce surge damage. Also adding supplementary equipment grounding electrodes for the PV array mounting racks/module frames as shown in figures 1 and 2 and not bonding them to other grounding electrodes may reduce the potential for lightning damage (see NEC, 250.54).

Fine Stranded Cables

If you are in another industry that uses these conductors and associated connectors improperly, or you inspect such equipment, notifying UL might get some additional corrective actions taken. Inspectors can contact UL and file a field report at the following UL web site: (https://www.ul.com/regulators/ahjprod.cfm). Others can file a report to UL at this site: (https://www.ul.com/consumers/conproddb.cfm). I can supply a PDF of the original article, if needed.

Germany Does It Right

The electricians that I talked with were familiar with the use of fine stranded conductors and the equipment-production facilities I visited used them regularly. All locations had a wide range of crimp-on wire-end ferrules and sleeves available, and they also had the proper crimping tools for placing these devices on fine stranded cables before inserting them into terminals. Even the building supply stores (equivalent to Home Depot and Lowes) had these ferrules readily available (photo 3).

Photo 3. Ferrules on the shelf

I discovered that the typical residential and commercial wiring in Germany is accomplished with a jacketed, sheathed, three-four conductor cable where each of the main conductors consists of flexible, fine stranded wires (photo 4). These types of cables have been used for decades. Where our type NM cables typically have solid conductors up to 10 AWG, the German equivalents use fine stranded flexible conductors. The German electric dryer and range cords use fine stranding like ours do, but theirs have ferrules attached (photo 5).

Photo 4. Fine stranded cables used for residential wiring

Photo 5. Ferrules installed on dryer cord

It appears that the lack of familiarity with the proper use of fine-stranded cables here in the U.S. can possibly be traced to the fact that the typical electrician (and home owner) rarely deals with these cables. In Germany, where these cables are used daily, everyone seems to know how to properly install them. I wish we could import that knowledge base to the U.S. (along with the excellent German rail system).

For Additional Information

If this article has raised questions, do not hesitate to contact the author by phone or e-mail. E-mail:jwiles@nmsu.edu; Phone: 505-646-6105

1 A PV Systems Inspector/Installer Checklist will be sent via e-mail to those requesting it. A draft copy of the 143-page, 2005 edition of the Photovoltaic Power Systems and the National Electrical Code: Suggested Practices, published by Sandia National Laboratories and written by the author, may be downloaded from this web site (http://www.nmsu.edu/~tdi/roswell-8opt.pdf.) The Southwest Technology Development web site (http://www.nmsu.edu/~tdi) maintains all copies of the “Code Corner Columns” written by the author and published in Home Power Magazine over the last ten years. Copies of previous “Perspectives on PV” are also available on this web site.

The author makes 6–8 hour presentations on “PV Systems and the NEC” to groups of 40 or more inspectors, electricians, electrical contractors, and PV professionals for a very nominal cost on an as-requested basis.

John Wiles
John Wiles retired in April 2013 as a Senior Research Engineer at the Southwest Technology Development Institute at New Mexico State University. However, he works part time as 25% employee and continues to assist the PV industry, electrical contractors, electrical inspectors, and purchasing agencies in understanding the PV requirements of the National Electrical Code (NEC). He is an active member on six UL Standards Technical Panels. John served as Secretary for the PV Industry Forum involved with Article 690 of the NEC. Over 30 submissions were accepted for the 2011 NEC and 55 proposals were submitted for the 2014 Code. He drafted the text for Article 690 in the 2005 NEC Handbook and 2008 NEC Handbook. Fieldwork involves balance of systems design for PV systems, inspections and acceptance testing of PV systems, test and evaluation of PV components, and the design and installation of data acquisition systems. He bought his first codebook in 1960 and installed his first PV system in 1984. He lived in an off-grid, PV/wind-powered home (permitted and inspected, of course) with his wife Patti, two dogs, and a cat for more than 16 years. His retirement home currently has a 8.5 kW utility-interactive PV system will full-house battery backup and now has three dogs and two cats. He writes the “Perspectives on PV” series of articles for the International Association of Electrical Inspectors in their IAEI News magazine and has published an IAEI book on PV and the NEC for inspectors and plan reviewers. He has a Master of Science Degree in Electrical Engineering.