Where a Successful Installation Begins and Ends: Understanding NEC rules about wire temperature ratings, terminations

0
995

Most electrical inspectors are aware that confusion about wire temperature ratings and equipment termination temperature requirements will likely result in a rejected installation. Information about this topic can be found in the National Electrical Code (NEC), testing agency directories, product testing standards and manufacturers’ literature, but many electrical system installers and designers typically do not consult these resources until after their installation has been rejected.

While this can be a frustrating situation for the installer or designer, it can be equally frustrating for an electrical inspector, who could receive pointed questions about why an installation was flagged. Being armed with the facts about what the NEC says about wire temperature ratings and terminations can not only justify the judgment an inspector makes, but also creates an educational opportunity. In other words, an inspector who is willing to teach can help ensure that future installations are correctly approached by the installer or designer.

 

The importance of temperature ratings

Conductors are assigned a specific temperature rating based on the type of insulation utilized. Common insulation types can be found in Table 310.13 of the NEC, and corresponding ampacities can be found in Table 310.16. Table 1 in this article shows the ampacity of a 1/0 copper conductor based on different conductor insulation types. The ampacity depends on the temperature rating of the insulation. At the same ampacity, a smaller conductor with higher-rated insulation can be used instead of a larger conductor with lower-rated insulation. As a result, the amount of copper and even the number of conduit runs needed for the job may be reduced.

Table 1

One of the most common misapplications of conductor temperature ratings occurs when the established temperature rating of the equipment termination is ignored. This is particularly true for equipment rated for 600 V and lower, since it is tested as a complete system using conductors sized byNECrules. Reduced conductor sizes result in the system having less ability to dissipate heat, and therefore increases the operating temperature of the equipment terminations. Conductors must be sized by considering where they will terminate and how that termination is rated. If a termination is rated for 75°C, the maximum temperature at that termination should be 75°C when the equipment is loaded to its ampacity. If 60°C-insulated conductors are used in this example, the additional heat at the connection above 60°C could result in conductor insulation failure. When a conductor is selected to carry a specific load, the installer or designer must know the termination ratings for the equipment in the circuit.

Figure 1. Proper heat dissipation

For example, consider a circuit breaker with 75°C terminations and a 150-A load. If a THHN conductor (90°C) is chosen for the job, review Table 310.16 in theNECand look for a conductor that will carry 150 A. Although a 90°C conductor is being used, ampacity must be chosen from the 75°C column because the circuit breaker termination is rated at 75°C. Based on the table, a 1/0 copper conductor is acceptable. The installation would be as shown in figure 1, with proper heat dissipation at the termination as well as along the conductor length. Had the temperature rating of the termination not been a consideration, a 1 AWG conductor might have been chosen, based on the 90°C ampacity. This may have led to overheating at the termination or premature opening of the overcurrent device due to the smaller conductor size (see figure 2).

Figure 2. Improperly sized conductor

In this same example, a conductor with a 75°C insulation type (THW, RHW, USE, etc.) also would be acceptable since the termination is rated at 75°C. A 60°C insulation type (TW) is not acceptable since the temperature at the termination could rise to a value greater than the insulation rating.1

Equipment rated for 100 A or lower

For equipment with termination provisions for circuits rated 100 A or less or marked for 14 AWG through 1 AWG conductors,NEC110.14(C)(1)(a) items 1 thru 4 allow conductors to be used based on the following four conditions:

Figure 3. Conductors rated 60°C

1. Conductors rated for 60°C (see figure 3).

2. Conductors with higher temperature ratings provided the ampacity is determined based on the 60°C ampacity of the conductor (see figure 4).

3. Conductors with higher temperature ratings, provided the equipment is listed and identified for use with such conductors (see figure 5).

Figure 4. Conductors with higher temperature ratings

4. Conductors for specific motor applications (see figure 6). This permission is specific to Design B, C or D motors because those motors are temperature-evaluated with conductors based on 75°C ampacity according to National Electrical Manufacturers Association NEMA MG-2.2

Equipment rated higher than 100 A

For equipment with termination provisions for circuits rated above 100 A or marked for conductors larger than 1 AWG,NEC110.14(C)(1)(b) items 1 and 2 allow conductors to be used based on the following conditions:

Figure 5. Conductor with higher temperature ratings

1. Conductors rated 75°C (see figure 7)

2. Conductors with higher than 75°C ratings, provided the conductor ampacity does not exceed the 75°C ampacity of the conductor size used (see figure 8). This condition also permits the conductors to be used at ampacities higher than 75°C if the equipment is listed and identified for the higher rating. However, for equipment rated 600V and lower, there is no listed equipment with termination ratings above 75°C.

Figure 6. Conductors for specific motor applications

The equipment termination ratings versus conductor insulation ratings are summarized in Table 2.

Caution on using lug ratings

When terminations are inside equipment such as panelboards, motor control centers, switchboards, enclosed circuit breakers and safety switches, it’s best to follow the temperature rating identified on the equipment labeling instead of the rating of the lug itself. Manufacturers commonly use 90°C-rated lugs on equipment rated only 60° or 75°C. Using the 90°C-rated lug in this type of equipment does not allow the installer to use 90°C wire at 90°C ampacity.

Figure 7. Conductors rated 75°C

Thus, electrical inspectors should encourage installers/designers to review device and equipment labeling for installation guidelines and possible restrictions.

Available equipment terminations

Keep in mind that a conductor has two ends, and that the termination on each end must be considered when applying the sizing rules. For example, consider a conductor wired to a 75°C termination on a circuit breaker at one end, and a 60°C termination on a receptacle at the other end. This circuit must be wired with a conductor that has an insulation rating of at least 75°C (due to the circuit breaker) and sized based on the ampacity of 60°C (due to the receptacle).

Figure 8. Conductors with higher temperature ratings

For electrical equipment rated for 600 V and less, terminations are typically rated at 60°C, 75°C or 60°/75°C. No distribution or utilization equipment is listed and identified for the use of 90°C wire at its 90°C ampacity. This includes distribution equipment, wiring devices, transformers, motor control devices and even utilization equipment such as HVAC, motors and light fixtures.

Table 2

In equipment rated higher than 600 V, the effect of the conductor as a heat sink is minimized, and ratings higher than 75°C are available.NEC110.40 recognizes that conductors with sizes based on the 90°C ampacity can be used in installations higher than 600 V. An example of how 90°C wire might be used at its 90°C ampacity is shown in figure 9. Note that the conductor does not terminate directly in the distribution equipment, but in a terminal or tap box using 90°C-rated terminations.

Figure 9. 90°C wire used at 90° ampacity

Frequently, manufacturers are asked when distribution equipment will be available with terminations that will permit 90°C conductors at 90°C ampacity. This would require not only significant equipment redesign (to handle the additional heat), but also coordination of downstream equipment … where the other end of the conductor terminates. Significant changes in the product testing/listing standards also would have to occur. A final note: Some equipment requires the conductors that are terminated in the equipment to have an insulation rating of 90°C but an ampacity based on 60 or 75°C. This type of equipment might include 100 percent-rated circuit breakers, fluorescent lighting fixtures, etc., and is marked to indicate such a requirement. Installers/designers should check with the manufacturer of the equipment to see if they need to take into account any special considerations.

Higher-rated conductors and derating factors

One advantage for conductors with higher insulation ratings is when derating factors are applied. This advantage is noted in the last sentence of NEC 110.14(c): “Conductors with temperature ratings higher than specified for terminations shall be permitted to be used for ampacity adjustment, correction, or both.” Derating factors may be required because of the number of conductors in a conduit, higher ambient temperatures or internal design requirements for a facility. By beginning the derating process at the ampacity of the conductor based on the higher insulation value, one may not be required to upsize the conductor to compensate for the derating. Installers/designers should bear in mind the following points (see the accompanying sidebar for an example):

• The ampacity value determined after applying the derating factors must beequal toorless thanthe ampacity of the conductor based on the temperature limitations at its terminations.

• The derated ampacity becomes the allowable ampacity of the conductor, and the conductor must be protected against overcurrent in accordance with this allowable ampacity.

Number of conductors per terminal

The NEC contains some key references regarding how many conductors can be terminated in a single terminal. NEC 110.14(A) has a blanket statement requiring that terminals for more than one conductor shall be so identified. This means that the terminal (or terminal bar) would have to be identified to accept more than one conductor. For equipment that contains a terminal or terminal bar, this identification is generally found on the wiring diagram or some other label on or inside the product.

In addition, the 2002 NEC added clarifying language regarding terminals for grounded conductors in panelboards. NEC 408.41 makes it clear that a terminal for a grounded conductor in a panelboard is acceptable for only one conductor. This NEC requirement correlates with a long-standing rule contained in Underwriters Laboratories UL 67 – Standard for Safety for Panelboards. One common mistake is for installers to misinterpret the marking found on many panelboards that allows multiple equipment grounding conductors in a single terminal to apply to grounded conductors as well. This NEC language will help installers/designers avoid this error at the outset rather than finding out from the electrical inspector at final installation. The added language also makes it clear that a terminal identified for more than one conductor can still be used for grounded conductors installed in parallel.


Derating Process Example

Assume a 480Y/277 V ac, three-phase, four-wire feeder circuit to a panelboard supplying 200 A for non-continuous fluorescent lighting load. Further assume that the conductors will be in a 40°C ambient temperature and the conductors originate and terminate in equipment with 75°C terminations.

Additional information to consider from the NEC:
• Since the phase and neutral conductors will be in the same conduit, consider the issue of conduit fill. NEC 310.15(B)(4)(c) states that the neutral must be considered to be a current-carrying conductor since a major portion of the load is a nonlinear load (i.e., electric discharge lighting).
• Based on this, four current-carrying conductors will be in the raceway. NEC 310.15(B)(2)(a) requires a 20-percent reduction in the conductor ampacity based on having four to six current-carrying conductors in the raceway.
• According to the ambient correction factors at the bottom of Table 310.16, an adjustment of 0.88 for 75°C and 0.91 for 90°C must be made.

The calculations, using a 75°C conductor such as THWN, are as follows:
• 300 kcmil copper has a 75°C ampacity of 285 A
• Using the factors noted earlier: 285 A x 0.80 x 0.88 = 201 A
The allowable ampacity of the 300 kcmil copper conductor for this circuit is 201 A. Had the derating factors for conduit fill and ambient not been required, a 3/0 copper conductor would have met the needs for this application.
The calculations using a 90°C conductor such as THHN are as follows:
• 250 kcmil copper has a 90°C ampacity of 290 A
• Using the factors noted earlier: 290 A x 0.80 x 0.91 = 211 A

Thus, 211 A is less than the 75°C ampacity of a 250 kcmil copper conductor (255 A), so the 211 A would now be the allowable ampacity of the 250 kcmil conductor. Had the calculation resulted in a number larger than the 75°C ampacity, the actual 75°C ampacity would have been used as the allowable ampacity of the conductor. This is critical, since the terminations are rated at 75°C. Note that the conductor size was reduced by one size (300 kcmil to 250 kcmil) and still accommodated all of the required derating factors for the circuit. This is the primary advantage of using 90°C conductors.

Therefore, when using 90°C wire for derating purposes, derating can begin at the 90°C ampacity. One must compare the result of the calculation to the ampacity of the conductor based on the termination rating (60° or 75°C). The smaller of the two numbers then becomes the allowable ampacity of the conductor.

Note that in the 2002 NEC, a change was made to add the last sentence to 110.14(C)(1) that states “Unless the equipment is listed and marked otherwise, conductor ampacities used in determining equipment termination provisions shall be based on Table 310.16 as appropriately modified by 310.15(B)(1) through (6).” This sentence makes it clear that the ampacities of conductors at terminations are to be based on Table 310.16 and not the other tables in Article 310. Other tables may be applicable for the conductors in a specific environment, but in all cases, the ampacity at the termination must be based on Table 310.16. For instance, a single conductor installed in free-air may have its ampacity determined by Table 310.17. Examples of those circumstances where this may be useful include ambient derating and installation in a cable tray (see Article 392). However, at the point where the conductor is terminated in equipment, the ampacities of Table 310.16 will govern. This may require that a larger conductor be used or that the conductor size be changed prior to entering the equipment.


Final thoughts

Proper termination of conductors is a critical part of a safe electrical installation. The ampacity assignment of a conductor is impacted by not only the physical characteristics of the conductor, but the connected equipment as well. Inspectors that are intimately aware of the appropriateNECrules are in the position to educate installers and designers so they can avoid a rejected installation, but more importantly, help ensure proper terminations in the future.

References

1. The equipment sizes and ampacities shown in the figures are arbitrary. The rules apply to any equipment rated 100 A or lower.

2. Safety Standard for Construction and Guide for Selection, Installation, and Use of Electric Motors and Generators

3. Underwriters Laboratories®General Information on Electrical Equipment Directory states the following about terminations: “A 75°C or 90°C temperature marking on a terminal (e.g., AL7, CU7AL, AL7CU or AL9, CU9AL, AL9CU) does not in itself indicate that a 75°C or 90°C insulated wire can be used unless the equipment in which the terminals are installed is marked for 75°C or 90°C.”

Previous articleNote from the CEO/Executive Director — City of Dallas, Texas, cuts about 36% of building inspection staff
Next articleConnecting the Inverter
jim.pauley@us.schneider-electric.com'
Jim Pauley was named President and Chief Executive Officer of the National Fire Protection Association (NFPA) in 2014. NFPA is a global, nonprofit organization devoted to eliminating death, injury, property and economic loss due to fire, electrical and related hazards. Prior to joining NFPA, Mr. Pauley concluded a 30 year career in the electrical and energy industry where he most recently served as Senior Vice President, External Affairs and Government Relations for Schneider Electric. During his career, Jim was actively involved in NFPA serving in various capacities including chairman of the NFPA Standards Council. Mr. Pauley has served in a number of leadership positions including chairman of the board for the American National Standards Institute (ANSI) and chair of the High Performance Building Council for the National Electrical Manufacturers Association (NEMA). He has received numerous awards and recognitions including his recent induction into the Engineering Hall of Distinction at the University of Kentucky. He holds a bachelor’s degree in Electrical Engineering from the University of Kentucky and is a licensed professional engineer.